MultiFlame - 3IR Flame detector

The MultiFlame DM-TV6-T is a multi-spectrum infrared flame detector using three wavelenghts. DM-TV6-T responds to hydrocarbon fires and is the right choice for operation in dirty enviroments or for detection of smokey fires.

Flame detectors - MultiFlame - 3IR Flame detector

Features

The DM-TV6-T is designed to respond to unwanted hydrocarbon fires, whilst maintaining a high degree of false alarm immunity.
The device offers a wide range of output options, as standard and is suitable for use in SIL 2 applications.  The unit may be interfaced directly with a wide range of fire panels, controllers and PLC's etc.
The unit is fully configurable using a wireless handheld terminal (TLU) giving true flexibility to the installer.  Time delays, sensitivity and output configuration are all set up via the TLU, hazardous area approved handheld unit.
Wireless testing of the optical and output circuits is also possible using the TLU too.

Application

 

  • Refineries
  • Drilling and Production Platforms
  • Fuel Loading Facilities
  • Compressor Stations
  • LNG/LPG Processing and Storage
  • Gas Turbines
  • Chemical Plants
  • Aircraft Hangars
  • Sports Stadia / Atria

 

Specification
General
Technology Multi-spectrum Infrared
Fire Types Hydrocarbon fires
Range, n-heptane 80m (260 ft) 0.3x0.3m (1 sq ft)
Range, gasoline 65 m (210 ft) 0.3x0.3 m (1 sq ft)
Output Signal
Standard 4-20mA, max. load impedance 700? (Std.)
PLC option 0-22mA (Option for PLC’s)
Syntel Lonworks
Alarms 2 x configurable Relays max 1A / 30V
Electrical
Power supply 24V DC, range (18 - 32V DC)
Power consumption 70 mA normal; 155 mA during test
Connection 0.3 mm2 (22 AWG) - 2.5 mm2 (12 AWG)
Environmental
Storage: -40°C to +70°C (-40°F to 158°F)
Operation -20°C to +60°C (-4°F to 140°F)
Humidity 95% RH (non-condensing)
Ingress IP66
RFI/EMI Complies with EN50081-1, EN50081-2,
EN50082-1 and EN50082-2.
Explosion Proof Housing
Material Epoxy coated aluminium (std)
316 L stainless steel (option)
Approvals
ATEX ATEX II 2 G EEx d II C T6
Certificate: LCIE03ATEX6263
IECEx IECEx LCI09.0018

© SIMTRONICS group

www.kingdesign.no